SPI 3
Connection of Serial Devices to PROFIBUS
By using the SPI 3, devices with serial interface are integrated in PROFIBUS as DP slaves. Depending on the application, various protocols and physical interfaces are available. In decentralized PROFIBUS installations, the SPI 3 replaces the serial interface inside the PLC.
The SPI 3 is configured via the respective PROFIBUS DP master by means of the SPI 3 GSE file. The PROFIBUS I/O range can be flexibly configured.
The SPI 3 is suitable for simple applications, such as connecting text displays or barcode scanners, as well as for more complex applications such as the integration of identification systems, scales, controllers and laboratory equipment.
Benefits
- Easy installation and parameterization
- Configuration without additional software
- Flexible configuration of PROFIBUS I/O range
Functions
- DP slave with a transmission rate of 9.6 kBit/s up to 12 MBit/s
- Serial transmission rate 110 Bit/s up to 57.6 kBit/s (depending on the protocol)
- Serial interfaces RS 232, RS 422 or RS 485 available
- Configuration with GSE file via the PROFIBUS DP master
- Plug & play integration into PROFIBUS
- I/O range configurable from 2 to 64 data words
Technical Data
| Nominal supply voltage | 24 V DC (19,2 … 28,8) |
| Current consumption | max. 200 mA |
| Ambient temperature range | 0 … +60°C |
| Transmission rate serial | 110 Bit/s bis 57,6 kBit/s (depending on protocol) |
| Interface serial | RS 232, RS 422, RS 485 (interface as per order) |
| Protocols serial | free ASCII driver, 3964R, RK512, MODBUS RTU |
| Transmission rate PROFIBUS | 9,6 kBit/s to 12 MBit/s |
| Interface PROFIBUS | RS 485 |
| I/O Range PROFIBUS | 2, 4, 8, 16, 32, 64 data words (depending on protocol) |
| Case, protection class | Plastic, IP 20 |
| Mounting | 35 mm DIN top hat rail |
| Dimensions W x H x D | 75 x 75 x 53 mm |
| Weight | 136 g |
| Certificate | CE, UL |
Scope of Delivery
- SPI 3
- Installation Guide
By Download
- Docu + Media Kit (includes online documentation, GSE, function blocks for SIMATIC S5 and S7, example projects)
- Release Note
Order Information
|
|
Quick Links
News
Parallel monitoring of fieldbus and field devices